کنترل پنل هوشمند 2لوپ 2-7002|یونیپاس
Technical data
Fire alarm loops
2 signal-
power 1-
Addressable devices in one signal loop Up to 125
Cross section of the signal loop wire (0.82.5) mm2
Maximum resistance of the signal loop 100Ω
Number of devices in one branch Up to 32
Fire alarm zones Up to 250
Addressable devices in one zone Up to 60
Response time to activated detector signal Up to 10 seconds
Registered events by the counter of fire events Up to 9999
Archive of events Op to 1023 Power supply :
mains- 220/230VAC, 50/60Hz
backup batteries 2x12 VDC, 18Ah
Current consumption of power supply loopUp to 1A
Outputs:
relay
30VDC/1A 3
controllable
28V DC/1A 2
auxiliary
supply 24VDC/1A 1
Interfaces:
RS
232 or RS 485 1
CAN
2
Dimensions 480 x 445 x 100 mm
Weight (batteries not included) 7.1 kg
Operating temperature Minus 5oC to 40oC
Relative humidity (93±3) % at 40oC
Degree of protection IP 40